Direct answer: according to the inspection requirements, focus on the inspection of oil unloading port, oil and gas recovery port, end cover of man-made oil measuring port, liquid collecting tank port, pressure vacuum valve of discharge pipe, oil and gas recovery pipeline, oil and gas recovery system of oil tanker and coupling valve. The oil and gas concentration at each point shall not be higher than 500 micromole per mole. The portable testing instrument shall be used to scan point by point, and the point of reading exceeding the limit shall be up to standard by replacing the sealing ring, improving the sealing method or replacing parts. This test is a fixed action of environmental protection investigation, and the site can self-check according to the point list.
Go through the system again, and all connection points that may leak are points. The end cover and joint of the oil discharge port are the first-the seal wears fastest every time the oil is discharged. The oil and gas recovery port and the coupling valve are the second, and the connection state directly determines the sealing effect. The end cover of the man-made oil outlet is the third, which should be checked at ordinary times. The liquid collecting tank mouth and the discharge pipe valve are the fourth, often failing due to liquid accumulation and scaling. The oil and gas recovery system of the tanker belongs to the fifth, both sides must be recognized. According to the list number one by one, the corresponding point number of the test record will be compared in the next recheck.
| Location point | Source of leakage | disposal method | Key points of re-inspection |
|---|---|---|---|
| Oil discharge port end cover joint | Removal and installation wear | Replace the sealing ring | Comparison before and after the same point |
| Oil and gas recovery port | Connection not in place | Improved connection | Analog connection status measurement |
| End cover of oil dosing port | Closed lax | Replace end cap pad | Test after tightening the cover |
| Liquid collecting tank mouth | Effusion scaling | Clean and replace seal | Re-test after cleaning |
| P/V valve | The valve core does not return to the seat | Maintenance or replacement | Post-action test |
| Coupling valve | Contact surface wear | Replace the seal | Test in connected state |
Use a portable oil and gas concentration detector on site to slowly move samples at the point sealing surface, end cover gap and valve stem, and record when the reading is stable. Before testing, make sure that the range of the instrument covers the expected concentration within the validity period of calibration. There are two main points in the operation method: first, the instrument probe should be as close as possible to the suspicious sealing surface but should not touch it to avoid contaminating the probe; The second is to record the reading of each point after it is stable, and the peak value in movement is not counted. During the test, the system remains in a normal operating state-qualified in the shutdown state does not mean that the operating state is qualified.
The handling process must be a closed loop: after replacing the sealing ring, retest at the same measurement point, and only when the data falls below the limit can the task be considered complete. For locations that repeatedly exceed the limit, investigate at the next higher level—check whether the sealing method is incorrect or the component selection is inappropriate; simply replacing the seal ring only addresses the symptoms, not the root cause. Making point-of-sale inspections a monthly self‑inspection item is far more effective than last‑minute cramming before an official inspection.
Portable detection solves the problem of "whether there is super" and daily inspection solves the problem of "where may be super. The smell of oil smelled during refueling, traces of oil and dust on the sealing surface, and whether the end cover is properly covered with hands, these signals from naked eyes and nose can narrow the detection range to several points. Combination of the two: suspicious points are found during patrol inspection, confirmed by the instrument, and retested after disposal. Only by the instrument does not patrol, the point number does not match the scene; Only patrol inspection does not detect, subjective judgment cannot replace data.
According to the investigation requirements, the reading of the testing instrument at the on-site point shall prevail. If it exceeds the standard, the point is determined to be inconsistent, and the point position shall be remeasured for confirmation after disposal.
Sure. Equipped with portable oil and gas concentration detector and operated according to regulations, the instrument can be self-checked. The instrument shall be within the validity period of calibration, and the operator can get started with simple training.
It belongs to the handover interface, and the carrier shall be notified to rectify the problems found in the site inspection. It is better to specify the responsibilities and rectification time limit of both parties in the agreement.
This article is organized by Luoyang wohong petrochemical equipment co., ltd. the company provides design, manufacture, installation, commissioning and operation and maintenance services for oil and gas recovery equipment, solvent recovery devices and buried composite pipe networks at gas stations, oil depots and chemical enterprises. if you need scheme configuration or on-site investigation, please contact and exchange.
Company Name:
Luoyang Wohong Petrochemical Equipment Co., Ltd
Hotline:
13526990215
Company Address:
W2-1, Dongda Technology Industrial Park, Luoxin Industrial Cluster, Xin'an County, Luoyang City
E-mail
lixiang@vohonoilpipe.com
Scan to follow us
Luoyang Wohong Petrochemical Equipment Co., Ltd Powered by EyouCms Henan ICP Registration No. 17014668-11 sitemap.xml